CyrusOne

1649 W Frankford Road

Carrollton, TX

DFW1

COLOCATION

About DFW1 Data Center

OVERVIEW


DFW1 is a colocation data center in Carrollton operated by CyrusOne. The data center is a 670,000 SF retrofit facility. Carriers such as tw telecom, Time Warner Cable and Alpheus are connected to the data center in addition to IBM Cloud, Megaport and PacketFabric cloud services. Infrastructure redundancies include N+1 for cooling and N/2N for UPS.

1Q23 Dallas/Fort Worth Data Center Market Report

POWER


??? NN

Commissioned Power

??? NN

Available Power

Login to view capacity data

??? NN

Under Construction Power

??? NN

Planned Power

  • Estimated Power Cost
    $0.060 - 0.070
  • Single or Dual Feed
    Dual Feed
  • On-Site Substation
    No
  • Power Provider
    Oncor
  • Number of Substations
    Two
  • Estimated kW/Cabinet
    --
  • Additional Information
    --

BUILDING


??? ??

Commissioned Space

??? ??

Available Space

Login to view capacity data

??? ??

Under Construction Space

??? ??

Planned Space

  • Status
    Operational
  • Building Size
    670000 SF
  • Year Built
    2000
  • Building Floors
    2
  • Building Owner
    CyrusOne
  • Purpose Built or Retrofit
    Retrofit
  • On-Site Office Space
    Yes
  • On-Site Conf Room
    Yes
  • On-Site Break Room
    Yes

GET A QUOTE

No Obligation. Free. Privacy Guaranteed.

Cabinet Requirements

Additional Options

Redundant power feed

Three-phase power


Committed Bandwidth*

Committed or "flat-rate" bandwidth is an unmetered connection where you can use any amount up to the limit for the same price every month.

Please enter the committed bandwidth amount

Burstable Bandwidth

Burstable or "fractional commit" is where you pay for a certain amount of bandwidth, but can utilize additional bandwidth as needed during times of peak demand. Additional charges will apply for utilizing bandwidth above the base level. E.g. "100 Mbps w/40Mbps Committed" or "20 Mbps burstable to 1000 Mbps"

{{ errors.first('burstableBandwidth') }}

Contact Information

CONNECTIVITY


Provider (13) PoPs Services

INFRASTRUCTURE


  • UPS Redundancy
    N/2N
  • UPS Description
    750 kVA Mitsubishi UPS systems; each power leg has a dedicated UPS with battery backup
  • Generator Redundancy
    2N
  • Generator Description
    Scalable 2.25 MW Detroit Diesel dedicated generators pre-wired for additional capacity; 6,000 gallon belly tank per generator
  • Cooling Redundancy
    N+1
  • Cooling Description
    Hybrid indirect evaporative cooling system capable of offering 80% free cooling; highly-efficient multiple 500-ton Direct Evaporative Cooling Units with rapid restart and adaptive controlled microprocessors (with ability to scale as density increases); backup water tanks with 48-hour capacity at a full load

COMPLIANCE


  • --

    SSAE-16
  • --

    SSAE-18
  • --

    HIPAA
  • --

    PCI
  • --

    DIACAP
  • --

    Energy Star
  • --

    ISO
  • --

    FISMA
  • --

    FEDRAMP
  • --

    NIST
  • --

    SOC 1
  • --

    SOC 2
  • --

    SOC 3
  • --

    Uptime Institute MO Site Award
  • --

    Uptime Institute Tier III Constructed
  • --

    Uptime Institute Tier III Design

SERVICES


  • --

    Private Suites
  • --

    Dedicated Infrastructure
  • --

    Cloud
  • SLA 99.9%

SECURITY


  • --

    Perimeter Fencing
  • --

    Card Key Access
  • --

    CCTV
  • --

    Man Trap
Clear All

BACK TO PROFILE

REQUEST A QUOTE FROM CyrusOne DFW1 FACILITY

Tell us a little about your needs before we connect you with a CyrusOne representative.

DATA CENTER REQUIREMENTS


BASIC INFORMATION


By clicking send, I agree that datacenterHawk will send this information to CyrusOne.

SEND QUOTE

GET A QUOTE