Cyxtera Technologies

615 N. 48th Street

Phoenix, AZ

PHX1-A,B,C

COLOCATION

About PHX1-A,B,C Data Center

OVERVIEW


This Cyxtera Technologies facility is located at 615 N. 48th Street in Phoenix. This facility is retrofit and currently offers 12,325 kW of critical power to data center customers. PHX1-A,B,C currently offers fiber connectivity to AT&T, Verizon Communications and Cox Enterprises. Backup generators are configured as 2N.

1Q23 Phoenix Data Center Market Report

POWER


??? NN

Commissioned Power

??? NN

Available Power

Login to view capacity data

??? NN

Under Construction Power

??? NN

Planned Power

  • Estimated Power Cost
    $0.070 - 0.080
  • Single or Dual Feed
    Dual Feed
  • On-Site Substation
    Yes
  • Power Provider
    Arizona Public Service Electric Co.
  • Number of Substations
    More
  • Estimated kW/Cabinet
    20.00 - 20.00
  • Additional Information
    --

BUILDING


??? ??

Commissioned Space

??? ??

Available Space

Login to view capacity data

??? ??

Under Construction Space

??? ??

Planned Space

  • Status
    Operational
  • Building Size
    538056 SF
  • Year Built
    2006
  • Building Floors
    1
  • Building Owner
    Iron Mountain
  • Purpose Built or Retrofit
    Retrofit
  • On-Site Office Space
    Yes
  • On-Site Conf Room
    Yes
  • On-Site Break Room
    Yes

GET A QUOTE

No Obligation. Free. Privacy Guaranteed.

Cabinet Requirements

Additional Options

Redundant power feed

Three-phase power


Committed Bandwidth*

Committed or "flat-rate" bandwidth is an unmetered connection where you can use any amount up to the limit for the same price every month.

Please enter the committed bandwidth amount

Burstable Bandwidth

Burstable or "fractional commit" is where you pay for a certain amount of bandwidth, but can utilize additional bandwidth as needed during times of peak demand. Additional charges will apply for utilizing bandwidth above the base level. E.g. "100 Mbps w/40Mbps Committed" or "20 Mbps burstable to 1000 Mbps"

{{ errors.first('burstableBandwidth') }}

Contact Information

CONNECTIVITY


Provider (36) PoPs Services

INFRASTRUCTURE


  • UPS Redundancy
    N+1
  • UPS Description
    Power Conditioning Modular UPS deployed in 1.5 MWA increments; UPS type: Toshiba and Eaton
  • Generator Redundancy
    2N
  • Generator Description
    Twenty-four (24) 2.5 MW Caterpillar generators; 52 MW generator capacity for the building; 72-hour diesel fuel runtime at full load
  • Cooling Redundancy
    N+1
  • Cooling Description
    Redundant 10,000-ton chilled water plant; temperature ranges between 59-90 degrees Fahrenheit; hot/cold aisle containment

COMPLIANCE


  • --

    SSAE-16
  • --

    SSAE-18
  • --

    HIPAA
  • --

    PCI
  • --

    DIACAP
  • --

    Energy Star
  • --

    ISO
  • --

    FISMA
  • --

    FEDRAMP
  • --

    NIST
  • --

    SOC 1
  • --

    SOC 2
  • --

    SOC 3
  • --

    Uptime Institute MO Site Award
  • --

    Uptime Institute Tier III Constructed
  • --

    Uptime Institute Tier III Design

SERVICES


  • --

    Private Suites
  • --

    Dedicated Infrastructure
  • --

    Cloud
  • SLA 99.9%

SECURITY


  • --

    Perimeter Fencing
  • --

    Card Key Access
  • --

    CCTV
  • --

    Man Trap
Clear All

BACK TO PROFILE

REQUEST A QUOTE FROM Cyxtera Technologies PHX1-A,B,C FACILITY

Tell us a little about your needs before we connect you with a Cyxtera Technologies representative.

DATA CENTER REQUIREMENTS


BASIC INFORMATION


By clicking send, I agree that datacenterHawk will send this information to Cyxtera Technologies.

SEND QUOTE

GET A QUOTE