Equinix

105 Enterprise Avenue South

Secaucus, NJ

NY6

COLOCATION

About NY6 Data Center

OVERVIEW


NY6 is a colocation data center in Secaucus operated by Equinix. The facility comes in at 70,183 total SF. Cloud services from PacketFabric are available at the facility. To ensure continuity of service, the facility maintains N+1 generator redundancy.

1Q23 Northern New Jersey Data Center Market Report

POWER


??? NN

Commissioned Power

??? NN

Available Power

Login to view capacity data

??? NN

Under Construction Power

??? NN

Planned Power

  • Estimated Power Cost
    --
  • Single or Dual Feed
    Dual Feed
  • On-Site Substation
    No
  • Power Provider
    --
  • Number of Substations
    --
  • Estimated kW/Cabinet
    1800.00
  • Additional Information
    --

BUILDING


??? ??

Commissioned Space

??? ??

Available Space

Login to view capacity data

??? ??

Under Construction Space

??? ??

Planned Space

  • Status
    Operational
  • Building Size
    70183 SF
  • Year Built
    2015
  • Building Floors
    1
  • Building Owner
    Equinix
  • Purpose Built or Retrofit
    Purpose Built
  • On-Site Office Space
    Yes
  • On-Site Conf Room
    Yes
  • On-Site Break Room
    Yes

GET A QUOTE

No Obligation. Free. Privacy Guaranteed.

Cabinet Requirements

Additional Options

Redundant power feed

Three-phase power


Committed Bandwidth*

Committed or "flat-rate" bandwidth is an unmetered connection where you can use any amount up to the limit for the same price every month.

Please enter the committed bandwidth amount

Burstable Bandwidth

Burstable or "fractional commit" is where you pay for a certain amount of bandwidth, but can utilize additional bandwidth as needed during times of peak demand. Additional charges will apply for utilizing bandwidth above the base level. E.g. "100 Mbps w/40Mbps Committed" or "20 Mbps burstable to 1000 Mbps"

{{ errors.first('burstableBandwidth') }}

Contact Information

CONNECTIVITY


Provider (2) PoPs Services

INFRASTRUCTURE


  • UPS Redundancy
    2N
  • Generator Redundancy
    N+1
  • Generator Description
    Five (5) dedicated 2.5 MW generators, one (1) shared 2.5 MW swing generator supporting every 4 suites
  • Cooling Redundancy
    N+1
  • Cooling Description
    565 primary tons per 1,800 kW suite via Indirect Evaporative Rooftop Units; low energy indirect evaporative cooling system & hot aisle containment, reflective roof, LEDs, & optimized lighting controls; renewable energy - wind

COMPLIANCE


  • --

    SSAE-16
  • --

    SSAE-18
  • --

    HIPAA
  • --

    PCI
  • --

    DIACAP
  • --

    Energy Star
  • --

    ISO
  • --

    FISMA
  • --

    FEDRAMP
  • --

    NIST
  • --

    SOC 1
  • --

    SOC 2
  • --

    SOC 3
  • --

    Uptime Institute MO Site Award
  • --

    Uptime Institute Tier III Constructed
  • --

    Uptime Institute Tier III Design

SERVICES


  • --

    Private Suites
  • --

    Dedicated Infrastructure
  • --

    Cloud
  • SLA 99.9%

SECURITY


  • --

    Perimeter Fencing
  • --

    Card Key Access
  • --

    CCTV
  • --

    Man Trap
Clear All

BACK TO PROFILE

REQUEST A QUOTE FROM Equinix NY6 FACILITY

Tell us a little about your needs before we connect you with a Equinix representative.

DATA CENTER REQUIREMENTS


BASIC INFORMATION


By clicking send, I agree that datacenterHawk will send this information to Equinix.

SEND QUOTE

GET A QUOTE